Deep Sea DSE333 Auto Transfer Switch Control Module
Interchange part number:DSE333
Condition: New, Original
PLEASE NOTE: Genuine/Original parts do not provide return or exchange service.
KEY FEATURES
1.Volt-free relays 2. Supports many topologies
3. Automatic switch-over between supplies 4. Check sync feature
5.Real-time clock 5.10 configurable inputs
6.configurable outputs 7.Event log
8.Configurable timers
9.Automatic shutdown or warning when fault conditions are detected
10.PC configuration 11.Front panel configuration
12.LED indicators 13.The back-lit 4-line text LCD display
14.External mains (utility) or Genset failure inputs 15.Auto start inhibit
16.Load inhibit 17.Manual restore to mains
18.Optional current monitoring
KEY BENEFITS
Fully automatic monitoring and switch-over control minimizes the effects of power disruptions
The real-time clock provides accurate event information for easy maintenance diagnostics
User-friendly set-up and button layout
Will work with external synchronizer for a seamless return to mains
The real-time clock provides accurate event information for easy maintenance diagnostics
User-friendly set-up and button layout
Will work with external synchronizer for a seamless return to mains
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recover to 5 V. This is achieved without the need for internal batteries. LEDs and backlights will not be maintained during cranking.
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recover to 5 V. This is achieved without the need for internal batteries. LEDs and backlights will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
292 mA at 12 V, 167 mA at 24 V
292 mA at 12 V, 167 mA at 24 V
MAXIMUM STANDBY CURRENT
101 mA at 12 V, 66 mA at 24 V
MAINS (UTILITY)
101 mA at 12 V, 66 mA at 24 V
MAINS (UTILITY)
VOLTAGE RANGE
15 V to 333 V AC (L-N)
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
3.5 Hz to 75 Hz
OUTPUTS
OUTPUT A (MAINS/UTILITY)
Normally closed relay output
8 A AC at 250 V AC
Normally closed relay output
8 A AC at 250 V AC
OUTPUT B (GENERATOR)
Normally open volt-free output
8 A at 250 V AC
Normally open volt-free output
8 A at 250 V AC
OUTPUT C (START)
Normally closed volt-free output
8 A DC at 35 V DC (UL Rating 30 V)
Normally closed volt-free output
8 A DC at 35 V DC (UL Rating 30 V)
OUTPUT D (CHANGEOVER)
Normally open volt-free output
8 A at 250 V AC
Normally open volt-free output
8 A at 250 V AC
OUTPUT E
Normally open volt-free output
8 A at 250 V AC
GENERATOR
Normally open volt-free output
8 A at 250 V AC
GENERATOR
VOLTAGE RANGE
15 V to 333 V AC (L-N)
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
3.5 Hz to 75 Hz
MAGNETIC PICK UP